Three phase four wire class 0.1S energy meter for high-accuracy measurement on 3P4W circuits, with DLMS, Modbus and DNP3 communication.
Voltage Range80% - 120% Un
Current0.01A/0.05A (minimum)
Voltage Loop Power Consumption<1W/1VA (auxiliary power supply)
Frequency50Hz
Storage Temperature- 10 - 85℃
Active Power Accuracy0.1S
Product overview
Overview. The Reallin E3016 is a three phase four wire class 0.1S energy meter compliant with IEC 62052-11, designed for accurate measurement of active and reactive energy on 3P4W circuits.
Main characteristics. Accuracy is class 0.1S for active energy and 0.5S for reactive energy. It operates at 3P4W 3×57.7/100 to 240/415 V, with a voltage range of 80% to 120% Un and a frequency of 50 Hz. The minimum measurable current is 0.01 A or 0.05 A. It features a color configurable LCD display.
Interfaces and connectivity. The meter includes an optical port, an Ethernet port and multiple RS485 ports. Supported protocols are DLMS, Modbus and DNP3. It provides 5 signal inputs, 5 signal outputs and 2 relay outputs, together with an LED pulse output with a constant of 50000 imp/kWh and 50000 imp/kvarh.
Power and environment. The voltage loop consumes less than 1 W and 1 VA, with auxiliary power supply. Backup is provided by a replaceable battery and an internal supercapacitor with precise RTC. Working temperature ranges from -10 to 70 °C and storage temperature from -10 to 85 °C. Ingress protection is IP54 and insulation class is II.
Typical uses. The RS485 ports with Modbus and DNP3 protocols allow connection to PLCs, supervision systems and remote meter reading tools for consumption monitoring.
Integration. Dimensions are 272.0 × 174.5 × 80.5 mm and weight is about 1.9 kg. This product is available on quotation from Atlas Electronics.
Three phase four wire class 0.1S energy meter for high-accuracy measurement on 3P4W circuits, with DLMS, Modbus and DNP3 communication.
Voltage Range80% - 120% Un
Current0.01A/0.05A (minimum)
Voltage Loop Power Consumption<1W/1VA (auxiliary power supply)
Frequency50Hz
Storage Temperature- 10 - 85℃
2. Datasheet extract (recorded values)
Parameter
Value
Dimensions
272.0×174.5×80.5mm
Active Power Accuracy
0.1S
Communication Protocol
DLMS/Modbus/DNP3
Compliance Standard
IEC 62052-11
Current
0.01A/0.05A (minimum)
Display
color configurable LCD
Frequency
50Hz
Ingress Protection
IP54
Insulation Class
II
Model
E3016
Pulse Constant
50000imp/kWh, 50000imp/kvarh
Pulse Indication
LED
Reactive Power Accuracy
0.5S
Signal Inputs/Outputs
5 signal inputs, 5 signal outputs, and 2 relay outputs
Storage Temperature
- 10 - 85℃
Voltage
3P4W - 3×57.7/100 - 240/415V
Voltage Loop Power Consumption
<1W/1VA (auxiliary power supply)
Voltage Range
80% - 120% Un
Weight
about 1.9kg
Working temperature
- 10 - 70℃
Applications and use cases
Architectures in which 274814968 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for 274814968 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details