UEC1-65C
Three-pole AC power contactor 65 A

- Hold-in Power Consumption in VA
- 20 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm or 75mm DIN Rail
- Number of Units in Package 1
- 1 pcs
Three-pole AC power contactor 65 A
The Hongfa UEC1-65C is a three-pole power contactor with 3 NO contacts and an AC 50/60 Hz coil, designed for switching motors and power loads up to 690 V AC.
Hongfa UEC1-65C contactor. The Hongfa UEC1-65C is a three-pole power contactor (3P, 3 NO) from the UEC1 series, manufactured by Hongfa, designed for switching AC power circuits.
Main characteristics. Rated operational current Ie of 65 A in AC-3 at 400 V AC and 80 A in AC-1 at 690 V AC, conventional free air thermal current Ith of 80 A at 60 °C for the power circuit, rated insulation voltage Ui of 690 V and rated impulse withstand voltage Uimp of 6 kV according to IEC 60947. Average impedance of 1.5 mΩ for the power circuit.
Control circuit and coil. AC 50/60 Hz coil with control voltage Us from 24 to 415 V (values as listed), without built-in suppressor module. Inrush power of 105 VA and hold-in power of 20 VA at 25 °C. Operating range 0.8 to 1.1 Us at -40…60 °C.
Auxiliary contacts. Composition 1NO1NC, 2NO2NC or other combinations on request. Minimum switching current of 0.1 A and minimum switching voltage of 24 V for the signalling circuit.
Motors and endurance. Motor power of 18.5 kW at 220/230 V AC (AC-3), 30 kW at 380/400 V AC (AC-3) and 37 kW at 660/690 V AC (AC-3). Electrical durability of 0.9 million cycles at 65 A AC-3 and mechanical durability of 5 million cycles, with a maximum electrical operating rate of 400 cycles/h.
Environment and mounting. Operation from -40 to 60 °C, with derating from 60 to 70 °C, and storage from -60 to 80 °C. Operating altitude up to 3000 m without derating. IP20 front face protection according to IEC 60529, overvoltage category III. Mounting by screw or on 35 mm or 75 mm DIN rail. Screw clamp terminals for power (5 N·m) and control (1.2 N·m). Dimensions 63 × 112.5 × 132 mm, net weight 1.0 kg.
Standards and certifications. Conforming to IEC/EN 60947-4-1 and IEC/EN 60947-5-1, GB/T 14048.4 and GB/T 14048.5, UL 60947-4-1 and UL 60947-5-1. Certified CCC, CE, UKCA, VDE and UL (cULus), conforming to RoHS and REACh, mercury free.
Typical use. Switching of three-phase and single-phase motors and of resistive or inductive loads in industrial installations, in control and power panels. Available on quotation from Atlas Electronics.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC1-65C, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 80 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 1.5 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 80 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 132 mm |
| Device Short Name | UEC1-65C |
| Electrical Durability | 0.9 M cycles 65 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 112.5 mm |
| Hold-in Power Consumption in VA | 20 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 105 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 400 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 5 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 10 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 20 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 20 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 50 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 50 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 18.5 kW at 220/230 V AC 50/60 Hz (AC-3); 30 kW at 380/400 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm or 75mm DIN Rail |
| Net weight | 1.0 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 12 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...26 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 14.6 cm |
| Package 1 Length | 12.2 cm |
| Package 1 Weight | 1.05 kg |
| Package 1 Width | 7.2 cm |
| Package 2 Height | 18.8 cm |
| Package 2 Length | 41.5 cm |
| Package 2 Weight | 13.80 kg |
| Package 2 Width | 32.5 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL(cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 65 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 80 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 520 A ≤40 °C - 10 s for power circuit; 900 A ≤40 °C - 1 s for power circuit; 110 A ≤40 °C - 10 min for power circuit; 260 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 45 lb.in(5 N·m)- on bolt clamp terminals - with internal hexagon socket wrench 4 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 63 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC1-65C. For a missing document or a specific revision, our experts send it to you.
The Hongfa UEC1-65C is a three-pole power contactor with 3 NO contacts and an AC 50/60 Hz coil, designed for switching motors and power loads up to 690 V AC.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 80 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 1.5 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 80 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 132 mm |
| Device Short Name | UEC1-65C |
| Electrical Durability | 0.9 M cycles 65 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 112.5 mm |
| Hold-in Power Consumption in VA | 20 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 105 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 400 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 5 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 10 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 20 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 20 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 50 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 50 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 18.5 kW at 220/230 V AC 50/60 Hz (AC-3); 30 kW at 380/400 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm or 75mm DIN Rail |
| Net weight | 1.0 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 12 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...26 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 14.6 cm |
| Package 1 Length | 12.2 cm |
| Package 1 Weight | 1.05 kg |
| Package 1 Width | 7.2 cm |
| Package 2 Height | 18.8 cm |
| Package 2 Length | 41.5 cm |
| Package 2 Weight | 13.80 kg |
| Package 2 Width | 32.5 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL(cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 65 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 80 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 520 A ≤40 °C - 10 s for power circuit; 900 A ≤40 °C - 1 s for power circuit; 110 A ≤40 °C - 10 min for power circuit; 260 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 45 lb.in(5 N·m)- on bolt clamp terminals - with internal hexagon socket wrench 4 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 63 mm |
Answers to the questions that the recorded characteristics of UEC1-65C can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": 1NO1NC,2NO2NC,other combinations can be customized.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Three-pole AC power contactor 65 A




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC1-65C |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details