UEC1-65D
3-pole power contactor 65 A AC coil

- Hold-in Power Consumption in VA
- 20 VA 50/60 Hz (at 25 °C)
- Minimum Switching Current
- 0.1A for signalling circuit
- Mounting Support
- Screw; 35mm or 75mm DIN Rail
- Number of Units in Package 1
- 1 pcs
3-pole power contactor 65 A AC coil
Hongfa UEC1-65D three-pole power contactor for switching AC loads, rated 65 A in AC-3 utilisation category at 400 V.
Contactor. The Hongfa UEC1-65D is a three-pole power contactor from the UEC1 series, with 3 NO poles, designed for switching alternating current loads up to 690 V AC.
Main characteristics. Operational current of 65 A (at ≤ 60 °C) in AC-3 at ≤ 400 V and 80 A in AC-1 at ≤ 690 V, conventional free air thermal current of 80 A for the power circuit and 10 A for the signalling circuit. Average impedance of 1.5 mΩ, electrical durability of 1 million cycles at 65 A AC-3 and mechanical durability of 5 million cycles. Maximum operating rate of 600 cycles/h electrical and 3600 cycles/h mechanical.
Control circuit and coil. AC coil at 50/60 Hz, without built-in suppressor module, inrush power of 105 VA and hold-in power of 20 VA at 25 °C. Standard control voltages from 24 to 415 V AC. Auxiliary contacts 1NO+1NC, 2NO+2NC or other combinations on request. Associated fuse of 10 A gG for the signalling circuit and 80 A gG at ≤ 690 V coordination type 2 for the power circuit.
Motor power. Up to 18.5 kW at 220/230 V AC and 30 kW at 380/400 V AC in AC-3, and up to 37 kW at 660/690 V AC in AC-3. Rated short-time withstand current of 520 A for 10 s and 900 A for 1 s at ≤ 40 °C.
Compliance and installation. Conforming to IEC/EN 60947-4-1 and IEC/EN 60947-5-1, certified CCC, CE, UKCA, VDE and UL (cULus), IP20 front face protection, 850 °C fire resistance for current-carrying parts, operation from -40 to 60 °C and up to 3000 m altitude without derating. Mounting by screw or on 35 mm or 75 mm DIN rail. Dimensions 63 × 112.5 × 132 mm for a net weight of 1.0 kg. Designed to be combined with the auxiliary blocks and accessories of the CA1 range.
No published question about this part yet. Questions are reviewed before publication.
Every characteristic recorded for UEC1-65D, with where it comes from. Use the filters to find one quickly.
| Characteristic | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 80 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 1.5 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 80 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 132 mm |
| Device Short Name | UEC1-65D |
| Electrical Durability | 1 M cycles 65 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 112.5 mm |
| Hold-in Power Consumption in VA | 20 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 105 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 5 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 10 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 20 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 20 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 50 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 50 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 18.5 kW at 220/230 V AC 50/60 Hz (AC-3); 30 kW at 380/400 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm or 75mm DIN Rail |
| Net weight | 1.0 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 12 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...26 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 14.6 cm |
| Package 1 Length | 12.2 cm |
| Package 1 Weight | 1.05 kg |
| Package 1 Width | 7.2 cm |
| Package 2 Height | 18.8 cm |
| Package 2 Length | 41.5 cm |
| Package 2 Weight | 13.80 kg |
| Package 2 Width | 32.5 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL(cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 65 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 80 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 520 A ≤40 °C - 10 s for power circuit; 900 A ≤40 °C - 1 s for power circuit; 110 A ≤40 °C - 10 min for power circuit; 260 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 45 lb.in(5 N·m)- on bolt clamp terminals - with internal hexagon socket wrench 4 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 63 mm |
No specification matches.
Last verification : 2026-11-02
Official documents and the technical data recorded for UEC1-65D. For a missing document or a specific revision, our experts send it to you.
Hongfa UEC1-65D three-pole power contactor for switching AC loads, rated 65 A in AC-3 utilisation category at 400 V.
| Parameter | Value |
|---|---|
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 80 A gG at ≤ 690 V coordination type 2 for power circuit |
| Auxiliary Contact Composition | 1NO1NC,2NO2NC,other combinations can be customized |
| Average Impedance | 1.5 mΩ - Ith 50 Hz for power circuit |
| China RoHS Regulation | Conforming |
| Coil Technology | Without built-in suppressor module |
| Control Circuit Voltage Limits | 0.8...1.1 Us (-40…60 °C): operational AC 50 Hz; 0.85...1.1 Us (-40…60 °C): operational AC 60 Hz; 1...1.1 Us (60…70 °C): operational AC 50/60 Hz; 0.2...0.75 Us (-40…70 °C): drop-out AC 50/60 Hz |
| Control Dircuit Type | AC at 50/60 Hz standard |
| Conventional Free Air Thermal Current [Ith] | 80 A (at ≤60 °C) for power circuit; 10 A (at ≤60 °C) for signalling circuit |
| Depth | 132 mm |
| Device Short Name | UEC1-65D |
| Electrical Durability | 1 M cycles 65 A AC-3 at Ue ≤ 400 V |
| EU RoHS Directive | Conforming |
| Fire Resistance | Current-carrying parts:850 °C conforming to IEC 60695-2-11 |
| Height | 112.5 mm |
| Hold-in Power Consumption in VA | 20 VA 50/60 Hz (at 25 °C) |
| Inrush Power in VA | 105 VA 50/60 Hz (at 25 °C) |
| Insulation Resistance | > 10 MΩ for signalling circuit |
| IP Degree of Protection | IP20 front face conforming to IEC 60529 |
| Maximum Operating Rate | Electrical: 600 cycs/h; Mechanical: 3600 cycs/h |
| Mechanical Durability | 5 M cycles |
| Mercury Free | Yes |
| Minimum Switching Current | 0.1A for signalling circuit |
| Minimum Switching Voltage | 24 V for signalling circuit |
| Motor Power hp | 5 hp at 110…120 V AC 50/60 Hz for 1 phase motors; 10 hp at 200…208 V AC 50/60 Hz for 1 phase motors; 10 hp at 220…240 V AC 50/60 Hz for 1 phase motors; 20 hp at 200…208 V AC 50/60 Hz for 3 phases motors; 20 hp at 220…240 V AC 50/60 Hz for 3 phases motors; 50 hp at 440…480 V AC 50/60 Hz for 3 phases motors; 50 hp at 550…600 V AC 50/60 Hz for 3 phases motors |
| Motor Power kW | 18.5 kW at 220/230 V AC 50/60 Hz (AC-3); 30 kW at 380/400 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Mounting Support | Screw; 35mm or 75mm DIN Rail |
| Net weight | 1.0 kg |
| Number of Units in Package 1 | 1 pcs |
| Number of Units in Package 2 | 12 pcs |
| Operating Altitude | 0...3000 m without derating |
| Operating Time | Power circuit: 12...26 ms closing, 4...19 ms opening; Signalling circuit (NO): 15...26 ms closing, 4...19 ms opening; Signalling circuit (NC): 4...19 ms opening, 12...32 ms closing |
| Overvoltage category | III |
| Package 1 Height | 14.6 cm |
| Package 1 Length | 12.2 cm |
| Package 1 Weight | 1.05 kg |
| Package 1 Width | 7.2 cm |
| Package 2 Height | 18.8 cm |
| Package 2 Length | 41.5 cm |
| Package 2 Weight | 13.80 kg |
| Package 2 Width | 32.5 cm |
| Permissible Ambient Air; Temperature Around the Device | -40…60 °C for normal operating; 60…70 °C with derating (for operation in the range of Us...1.1Us); Storage: -60…80 °C |
| Pole Contact Composition | 3 NO |
| Poles Description | 3P |
| Product Certifications | CCC,CE,UKCA,VDE,UL(cULus LISTED) |
| Product or Component Type | Contactor |
| Product Series | UEC1 |
| Rated operational current (Ie) | 65 A (at ≤60 °C) at ≤ 400 V AC AC-3 for power circuit; 80 A (at ≤60 °C) at ≤ 690 V AC AC-1 for power circuit |
| Rated Operational Voltage (Ue) | Power circuit: ≤ 690 V AC 50/60Hz |
| Rated Short-Time Withstand Current [Icw] | 520 A ≤40 °C - 10 s for power circuit; 900 A ≤40 °C - 1 s for power circuit; 110 A ≤40 °C - 10 min for power circuit; 260 A ≤40 °C - 1 min for power circuit |
| REACh Regulation | Conforming |
| RoHS Exemption Information | Yes |
| Standards | GB/T 14048.4,GB/T 14048.5, IEC/EN 60947-4-1,IEC/EN 60947-5-1,; BS EN 60947-4-1,BS EN 60947-5-1,UL 60947-4-1,UL 60947-5-1 |
| Tightening torque | Power circuit: 45 lb.in(5 N·m)- on bolt clamp terminals - with internal hexagon socket wrench 4 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 11 lb.in(1.2 N·m)- on screw clamp terminals - with screwdriver Philips No 2 |
| [Ui] Rated Insulation Voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V UL Certified; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V UL Certified |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| Unit Type of Package 1 | 1 box |
| Unit Type of Package 2 | 1 carton |
| [Us] Control Circuit Voltage; (AC 50/60Hz) | Voltage (V): 24 36 42 48 110 115 127 220 230 240 380 400 415 |
| Utilisation Category | AC-3; AC-4; AC-1 |
| Width | 63 mm |
Answers to the questions that the recorded characteristics of UEC1-65D can answer. A question is not asked when nothing is recorded to answer it.
Yes — recorded under "Auxiliary Contact Composition": 1NO1NC,2NO2NC,other combinations can be customized.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
3-pole power contactor 65 A AC coil




Describe your application and constraints in a request.
What is recorded about the regulatory status and the life of this part.
| Current status | Status not stated |
| Key dates | Not recorded |
| Manufacturer part number | UEC1-65D |
| Manufacturer | Hongfa |
Power Contactors
1 Pole + Shunt 20A-40A Definite Purpose Contactor · Ref. : SA-1.5P
Price on request
Power Contactors
Three-pole power contactor 38 A AC-3 AC coil 50/60 Hz
Price on request
Power Contactors
Technical article: relay versus contactor differences
Price on request
Power Contactors
EPS box with integrated contactors for 1-phase/3-phase inverters · Ref. : X1/X3-EPS
Price on request
No advertising or analytics cookies. A single, strictly necessary cookie is set only if you sign in to your account. Your quote basket and comparison stay in your browser. Details