UEM5Z1-400 – 400 A molded case circuit breaker, 3P and 4P

400 A molded case circuit breaker, 3P and 4P

Molded Case Circuit Breakers

  • UEM5Z1
  • 400 A at 40 °C
  • 50 Hz
  • -40…70 °C
Manufacturer part number
UEM5Z1-400
Manufacturer
Hongfa
Range
UEM5Z1
Rated Current (In)
400 A at 40 °C

Hongfa UEM5Z1-400 molded case circuit breaker for AC distribution, 400 A rating, with LSIP thermal-magnetic trip unit and fixed, plug-in or withdrawable mounting.

Product overview

Overview. The Hongfa UEM5Z1-400 is a UEM5Z1 molded case circuit breaker for AC distribution at 50 Hz, conforming to EN/IEC 60947-2. It is offered in 3-pole or 4-pole versions with a rated current of 400 A at 40 °C.

Main characteristics. Rated operational voltage of 400 V AC 50 Hz and rated insulation voltage of 800 V AC 50 Hz, rated impulse withstand voltage of 8 kV, utilisation category B and pollution degree 3. The thermal-magnetic trip unit provides LSIP protection: long-time overload, short-time short-circuit, instantaneous short-circuit and pre-alarm. The long-time pick-up Ir is adjustable from 200 A to 400 A, the instantaneous pick-up Ii from 3 to 12 times In, and the short-time pick-up Isd from 2 to 12 times Ir. Breaking capacity is available as type M (Icu 65 kA, Ics 50 kA) or type H (Icu 85 kA, Ics 65 kA) at 400 V AC 50 Hz. Suitable for isolation, it offers 4000 mechanical cycles and 1000 electrical cycles at 400 V In.

Interfaces and accessories. The breaker accepts electrical accessories including shunt release, undervoltage release, auxiliary contacts and alarm contact, and can be operated by handle, motorized or rotary operating mechanism. It can be installed fixed, plug-in or withdrawable, horizontally or vertically flat on the back.

Power and environment. Operating ambient air temperature from -25 to 70 °C and storage from -40 to 70 °C, relative humidity 0 to 95 % at 25 °C, operating altitude up to 2000 m without derating. Dimensions: height 257 mm, depth 97 mm, width 140 mm for 3P and 184 mm for 4P, connection pitch 44 mm, net weight 5.7 kg for 3P and 7.5 kg for 4P.

Typical uses. Protection and isolation of distribution feeders and high-power circuits within an electrical enclosure, with manual or motorized control depending on the installation architecture.

Integration. Available on quotation from Atlas Electronics.

See all specifications

Highlights

  • Ambient Air Temperature for Operation: -25…70 °C
  • Ambient Air Temperature for Storage: -40…70 °C
  • Arcing Distance (mm): ≤50mm
  • Breaking Capacity: M、H
  • Connection Pitch: 44 mm
  • Depth: 97 mm

See also

Technical questions

Ask a question

No published question about this part yet. Questions are reviewed before publication.

Request a quote