Reallin MDVH3016 three-phase energy meter for 3P3W and 3P4W networks, class 0.1S for active energy and class 0.5S for reactive energy, with DLMS, Modbus and DNP3 communication.
Temperature range-Storage- 10 - 85℃
Voltage Range80%Un - 120%Un
Communication interface1*Optical Port
I/O interface5*Signal Inputs
Current circuit apparent power at In<1.3 VA
Maximum current Imax6A/20A
Product overview
Overview. The Reallin MDVH3016 is a three-phase three-wire and four-wire energy meter of class 0.1S for energy measurement. Accuracy is class 0.1S for active energy and class 0.5S for reactive energy.
Main characteristics. Rated voltage 3P4W 3×57.7/100 to 240/415 V and 3P3W 3×110 V, rated frequency 50 Hz, reference current In of 1 A or 5 A, maximum current Imax of 6 A or 20 A, starting current Ist of 0.1%In. Pulse constant of 50000 imp/kWh and 50000 imp/kvarh, LED pulse indicator, real-time clock compliant with IEC 62054-21 with replaceable battery and internal super capacitor. Color LCD display with configurable decimal places and backlight.
Interfaces and connectivity. One optical port and 5 signal inputs. Communication protocols DLMS, Modbus and DNP3, the latter two for SCADA systems.
Power and environment. Auxiliary supply of 50 to 280 V AC or DC, with auxiliary supply taking first priority. Apparent power of the current circuit below 1.3 VA. Operating temperature -10 to 70 °C, storage temperature -10 to 85 °C, protection degree IP 54, insulation class II. Dimensions 272.0 × 174.5 × 80.5 mm, weight about 1.9 kg.
Typical uses and integration. Energy measurement on three-phase networks, with integration into SCADA systems through the Modbus and DNP3 protocols and DLMS compatibility. Compliant with IEC 62052-11, IEC 62053-22/24, IEC 62056-21, IEC 62056-61 and IEC 62059-32-1. Available on quotation from Atlas Electronics.
Reallin MDVH3016 three-phase energy meter for 3P3W and 3P4W networks, class 0.1S for active energy and class 0.5S for reactive energy, with DLMS, Modbus and DNP3 communication.
Temperature range-Storage- 10 - 85℃
Voltage Range80%Un - 120%Un
Communication interface1*Optical Port
I/O interface5*Signal Inputs
Current circuit apparent power at In<1.3 VA
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class 0.1S for active; Class 0.5S for reactive
Auxiliary Supply Facility
Support auxiliary supply facility with 50 - 280V (AC or DC); AUX first priority
Backup power supply
Replaceable battery and internal super capacitor
Communication interface
1*Optical Port
Communication Protocol
DLMS/Modbus/DNP3 (Modbus & DNP3 is for SCADA)
Current circuit apparent power at In
<1.3 VA
Dimension(L×W ×D)
272.0×174.5×80.5mm
Environment
Operation- 10 - 70℃
I/O interface
5*Signal Inputs
Insulation Class
II
LCD display
Color display with configurable decimal places, backlight supported
Maximum current Imax
6A/20A
Minimum Current (Imin)
0.01A/0.05A
Protection degree
IP 54
Pulsating Indicator
LED
Pulsating(meter constant)
50000imp/kWh; 50000imp/kvarh
Rated Frequency Fn
50Hz
Rated Voltage Un
3P4W - 3×57.7/100 - 240/415V; 3P3W - 3×110V
Reference Current (In)
1A/5A
RTC
Provides RTC with clock accuracy according to IEC62054 - 21
Architectures in which 272033168 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for 272033168 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
272033168
Three-phase 0.1S class energy meter with optical port and DLMS support
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details