Three-phase three-wire or four-wire class 0.1S energy meter measuring active and reactive energy, with DLMS, Modbus and DNP3 communication for SCADA supervision.
Temperature range-Storage- 10 - 85℃
Voltage Range80%Un - 120%Un
Communication interface1*Optical Port
I/O interface5*Signal Inputs
Current circuit apparent power at In<1.3 VA
Maximum current Imax6A/20A
Product overview
Reallin MDVH3016. The Reallin MDVH3016 is a three-phase three-wire and four-wire energy meter designed to measure electrical parameters on distribution networks.
Measurement and accuracy. Class 0.1S for active energy and class 0.5S for reactive energy. Reference current In of 1 A or 5 A, maximum current Imax of 6 A or 20 A, starting current Ist of 0.1% In. Pulse constant of 50000 imp/kWh and 50000 imp/kvarh, rated frequency Fn of 50 Hz, voltage range of 80% Un to 120% Un.
Communication and inputs. One optical port, DLMS, Modbus and DNP3 protocols (Modbus and DNP3 for SCADA), 5 signal inputs. Real-time clock compliant with IEC 62054-21.
Power supply and environment. Auxiliary supply of 50 to 280 V AC or DC, replaceable battery and internal super capacitor as backup. Operating temperature -10 to 70 °C, storage temperature -10 to 85 °C, protection degree IP 54, insulation class II. Dimensions 272.0 × 174.5 × 80.5 mm, weight about 1.9 kg.
Typical uses. Remote supervision of electrical consumption in distribution boards, thanks to standardised communication protocols.
Standards. IEC 62052-11, IEC 62053-22/24, IEC 62056-21, IEC 62056-61, IEC 62059-32-1. Available on quotation from Atlas Electronics.
Three-phase three-wire or four-wire class 0.1S energy meter measuring active and reactive energy, with DLMS, Modbus and DNP3 communication for SCADA supervision.
Temperature range-Storage- 10 - 85℃
Voltage Range80%Un - 120%Un
Communication interface1*Optical Port
I/O interface5*Signal Inputs
Current circuit apparent power at In<1.3 VA
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
Class 0.1S for active; Class 0.5S for reactive
Auxiliary Supply Facility
Support auxiliary supply facility with 50 - 280V (AC or DC); AUX first priority
Backup power supply
Replaceable battery and internal super capacitor
Communication interface
1*Optical Port
Communication Protocol
DLMS/Modbus/DNP3 (Modbus & DNP3 is for SCADA)
Current circuit apparent power at In
<1.3 VA
Dimension(L×W ×D)
272.0×174.5×80.5mm
Environment
Operation- 10 - 70℃
I/O interface
5*Signal Inputs
Insulation Class
II
LCD display
Color display with configurable decimal places, backlight supported
Maximum current Imax
6A/20A
Protection degree
IP 54
Pulsating Indicator
LED
Pulsating(meter constant)
50000imp/kWh; 50000imp/kvarh
Rated Frequency Fn
50Hz
Rated Voltage Un
3P4W - 3×57.7/100 - 240/415V; 3P3W - 3×110V
Reference Current (In)
1A/5A
RTC
Provides RTC with clock accuracy according to IEC62054 - 21
Architectures in which 272690286 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
Solar production, storage and charging points on one site are often managed separately. Inverters, batteries, MPPT controllers, meters and chargers form a local energy system that shares production between users
To check
Regulatory framework for collective self-consumption in the country
Energy management system steering storage and charging
Metering accuracy for sharing between participants
Associated system blocks
ProductionStorageMeteringCharging
Need a complete solution?
Send a request for 272690286 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
272690286
Three-Phase Three-Wire/Four-Wire Class 0.1S Energy Meter
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details