Three phase intelligent electricity meter for measuring and recording energy consumption on a 3x230/400 V three phase AC system, with RS485 output and LCD display.
Temperature rangeoperation:-40-70℃
Voltage Range70%un~140%un
Communication interfaceRS485 port,up to38400 b ps
Current circuit apparent power at Ib<1VA
Maximum current Imax80A
Minimum Current (Imin)0.25A
Product overview
Reallin 3 Phase Intelligent Electricity Meter — three phase intelligent electricity meter designed to measure and record energy consumption on a three phase AC system.
Main characteristics. Rated voltage 3x230/400 V, rated frequency 50 Hz, voltage range 70% to 140% of Un, reference current Ib of 5 A and maximum current Imax of 80 A, starting current Ist of 0.4% Ib. Accuracy class B/1.0 for active energy and class 2.0 for reactive energy. Pulse constant of 1000 imp/kWh and 1000 imp/kvarh, indicated by an LED pulsating indicator.
Interfaces and connectivity. RS485 communication port up to 38400 bps for remote reading of metering data.
Power and environment. Voltage circuit consumption at most 1.5 W / 8 VA, current circuit apparent power below 1 VA at Ib. Operating temperature range -40 to 70 °C. Ingress protection IP51 in a protective enclosure. Insulation class II.
Display and dimensions. Dot matrix LCD with backlight supported. Dimensions 90 x 52.5 x 62 mm, weight about 0.3 kg. DIN rail mounting format.
Standards and compliance. EN 50470-3:2022, IEC 62053-21/23:2020, IEC 62052-31:2015, UL61010-1 and UL61010-2-030.
Typical uses. Energy consumption measurement on three phase networks, with data transmitted to a supervision system through the RS485 port.
Three phase intelligent electricity meter for measuring and recording energy consumption on a 3x230/400 V three phase AC system, with RS485 output and LCD display.
Temperature rangeoperation:-40-70℃
Voltage Range70%un~140%un
Communication interfaceRS485 port,up to38400 b ps
Current circuit apparent power at Ib<1VA
Maximum current Imax80A
2. Datasheet extract (recorded values)
Parameter
Value
Accuracy
class B/1.0 for active; class 2.0 for reactive
Communication interface
RS485 port,up to38400 b ps
Current circuit apparent power at Ib
<1VA
Dimension(LXW XD)
90x52.5x62mm
Insulation Class
II
LCD display
Dot Matrix type,backlight supported
Maximum current Imax
80A
Minimum Current (Imin)
0.25A
port ect ion Degree
IP51 in protective enclosure
Pulsating Indicator
LED
Pulsating(meter constant)
1000 imp/kwh; 1000 imp/kvarh
Rated Frequency Fn
50HZ
Rated Voltage Un
3x230/400v
Reference current Ib
5A
Standards
EN 50470-3:2022,IEC 62053-21/23:2020,IEC 62052-31:2015,UL61010-1,UL61010-2-030
Starting Current (Ist)
0.4%Ib
Temperature range
operation:-40-70℃
voltage circuit active lap parent power atun
≤ 1.5W/8VA
Voltage Range
70%un~140%un
Weight Of Meter
About0.3kg
Applications and use cases
Architectures in which 282180127 can play a role, derived from its category. This is not a compatibility statement: check the specifications against your requirements.
Energy bills give one total for the whole site. Submetering places meters and current sensors on each circuit or usage and collects their readings through a gateway, so consumption can be followed per building, floor or machine
To check
Number of circuits and phases to meter, and the current range of each
Wired Modbus bus or wireless LoRaWAN, depending on cabling access in the switchboards
Accuracy class required for internal allocation or for billing
A building’s energy, comfort and occupancy data sit in separate systems. Sensors, meters and gateways feed one model of the building, room by room, to compare scenarios and steer the installations
To check
Data model and building plans available
Software platform hosting the twin
Sensor density needed for a useful model
Associated system blocks
SensorsMetersGateways
Need a complete solution?
Send a request for 282180127 and the other parts of your project.
Similar parts to answer your needs. Compare the main characteristics. A recorded replacement is a documented relation; a similar product is a similarity only, never a compatibility claim.
Current productReallin
282180127
3 Phase Intelligent Electricity Meter, Class B, RS485
What is recorded about the regulatory status and the life of this part.
Regulatory compliance
No compliance statement is recorded for this part. Ask the supplier for the RoHS and REACH declarations and, for a radio product, the EU declaration of conformity.
With your consent, we use Google cookies to measure the site’s audience and our advertising. Your quote basket and comparison stay in your browser either way. Details